Constructions
1-Conductor | Fine-stranded copper (Class 5) |
2-Insulation | Cross linkable polyethylene (XLPE) |
3-Outer sheath | Polyvinyl chloride (PVC) |
1-Conductor | Fine-stranded copper (Class 5) |
2-Insulation | Cross linkable polyethylene (XLPE) |
3-Outer sheath | Polyvinyl chloride (PVC) |
Min. bending radius | 12 x D |
Max. operating temperature | 90° |
Max. short circuit temperature | 250° |
Rated voltage Uo/U | 0.6/1 kV |
AC test voltage | 3,5 kV |
Flame propagation test on single cable | EN 60332-1 |
Lead free | Pb |
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in | |
Conduit (A) | Air (A) | ||||
RV-K (0,6/1 kV) | |||||
1×2,5 | 6,2 | 54 | 7,98 | 29 | 29 |
1×4 | 6,7 | 70 | 4,95 | 66 | 40 |
1×6 | 7,3 | 90 | 3,30 | 82 | 53 |
1×10 | 8,2 | 133 | 1,91 | 109 | 74 |
1×16 | 9,2 | 189 | 1,21 | 139 | 101 |
1×25 | 11,0 | 284 | 0,780 | 179 | 135 |
1×35 | 12,1 | 381 | 0,554 | 213 | 169 |
1×50 | 13,08 | 517 | 0,386 | 251 | 207 |
1×70 | 15,7 | 712 | 0,272 | 307 | 268 |
1×95 | 17,6 | 923 | 0,206 | 366 | 328 |
1×120 | 19,2 | 1165 | 0,161 | 416 | 383 |
1×150 | 21,5 | 1446 | 0,129 | 465 | 444 |
1×185 | 23,9 | 1748 | 0,106 | 526 | 510 |
1×240 | 26,9 | 2280 | 0,0801 | 610 | 607 |
1×300 | 29,6 | 2829 | 0,0641 | 927 | 697 |
2×1,5 | 8,40 | 98 | 13,3 | 37 | 26 |
2×2,5 | 9,70 | 137 | 7,98 | 49 | 36 |
2×4 | 10,80 | 182 | 4,95 | 64 | 49 |
2×6 | 12,80 | 258 | 3,30 | 79 | 63 |
2×10 | 15,00 | 379 | 1,91 | 106 | 86 |
2×16 | 18,70 | 536 | 1,21 | 137 | 115 |
3×1,5 | 8,90 | 116 | 13,3 | 31 | 24 |
3×2,5 | 10,30 | 163 | 7,98 | 40 | 32 |
3×4 | 11,50 | 221 | 4,95 | 52 | 42 |
3×6 | 13,60 | 314 | 3,30 | 64 | 53 |
3×410 | 17,20 | 517 | 1,91 | 86 | 74 |
3×16 | 19,90 | 742 | 1,21 | 112 | 98 |
Flexible power and control cables designed for fixed applications.