NHXMH-O / NHXMH-J

Constructions

1-Conductor Solid or stranded copper (Class 1 or Class 2)
2-Insulation Cross linkable polyethylene (XLPE)
3-Filler Halogen free flame retardant (HFFR)
4-Outer sheath Halogen free flame retardant (HFFR)

Specifications

Min. bending radius 12 x D
Max. operating temperature 90°
Max. short circuit temperature 250°
Rated voltage Uo/U 300/500 V
AC test voltage 2 kV
Low smoke EN 61034
Halogen free EN 50525-1 – EN 50267
Flame propagation test on single cable EN 60332-3-24 Cat. C

Technical Data

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Air (A)
  NHXMH-O/NHXMH-J (300/500 V)
 2×1,5 8,3 101 12,1 22
 2×2,5 9,1 130 7,41 30
 2×4 10,4 182 4,61 40
 2×6 11,4 235 3,08 51
 2×10 14,2 379 1,83 70
2×16 16,8 548  1,15 98
 3×1,5 8,7 118 12,1 22
3×2,5 9,6 157  7,41 30
 3×4 11,0 224  4,61 40
 3×6 12,4 303  3,08 51
3×10 15,0 475 1,83 70
 3×16 18,2 711 1,15 98
 4×1,5 9,3 140 12,1 18,5
 4×2,5 10,3 189 7,41 25
 4×4 12,3 286 4,61 34
 4×6 13,9 389 3,08 43
 4×10 16,2 589 1,83 60
 4×16 19,8 888 1,15 80
4×25 24,0 1359  0,727 127
 4×35 26,7 1794 0,524 158
 5×1,5 10,0 165 12,1 18,5
5×2,5 11,1 224 7,41 25
5×4 13,6 353 4,61 34
 5×6 15,0 467  3,08 43
 5×10 17,6 714 1,83 60
 5×16 21,9 1098  1,15 80
5×25 26,1 1652 0,727 127
7×1,5 10,7 201 12,1 15,5
7×2,5 12,3 289 7,41 21

Applications

Used in refineries, hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, populated business centers where there is a risk of fire.

Standards