Constructions
1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
2-Insulation | Cross linkable polyethylene (XLPE) |
3-Outer sheath | Low smoke zero halogen (LSZH) |
1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
2-Insulation | Cross linkable polyethylene (XLPE) |
3-Outer sheath | Low smoke zero halogen (LSZH) |
Min. bending radius | x D ≤ 25 mm² |
Max. operating temperature | 90° |
Max. short circuit temperature | 250° |
Min. bending radius | 12 x D > 25 mm² |
Rated voltage Uo/U | 450/750 V – 600/1000 V |
AC test voltage | 2,5 kV – 3,5 kV |
Low smoke | EN 61034 |
Halogen free | EN 50525-1 – EN 50267 |
Flame propagation test on single cable | EN 60332-1 |
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in |
Conduit (A) | ||||
6181 B | ||||
1,5 | 4,4 | 31 | 12,1 | 23 |
2,5 | 4,8 | 42 | 7,41 | 31 |
4* | 5,7 | 63 | 4,61 | 42 |
6* | 6,2 | 83 | 3,08 | 54 |
10* | 7,3 | 125 | 1,83 | 75 |
16* | 8,5 | 183 | 1,15 | 100 |
25* | 9,7 | 276 | 0,727 | 133 |
35* | 10,9 | 374 | 0,524 | 164 |
50 | 13,2 | 522 | 0,387 | 198 |
70 | 14,7 | 722 | 0,268 | 253 |
95 | 17,2 | 997 | 0,193 | 306 |
120 | 19,1 | 1244 | 0,153 | 354 |
150 | 20,8 | 1515 | 0,124 | 393 |
185 | 23,0 | 1890 | 0,0991 | 449 |
240 | 26 | 2441 | 0,0754 | 528 |
300 | 28,8 | 3124 | 0,0601 | 603 |
Installation in wall, on boards and in channels or embedded in plaster. Low level of smoke emission and corrosive gasses in case of fire.