Constructions
1-Conductor | Fine-stranded copper (Class 5) |
2-Insulation | Cross linkable polyethylene (XLPE) |
3-Outer sheath | Low smoke zero halogen (LSZH) |
1-Conductor | Fine-stranded copper (Class 5) |
2-Insulation | Cross linkable polyethylene (XLPE) |
3-Outer sheath | Low smoke zero halogen (LSZH) |
Min. bending radius | 8 x D ≤ 25 mm² |
Max. operating temperature | 90° |
Max. short circuit temperature | 250° |
Min. bending radius | 12 x D > 25 mm² |
Rated voltage Uo/U | 450/750 V – 600/1000 V |
AC test voltage | 2,5 kV – 3,5 kV |
Low smoke | EN 61034 |
Halogen free | EN 50525-1 – EN 50267 |
Flame propagation test on single cable | EN 60332-1 |
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in |
Conduit (A) | ||||
6381 B | ||||
4* | 6,9 | 81 | 4,95 | 42 |
6* | 7,4 | 103 | 3,30 | 54 |
10* | 8,9 | 157 | 1,91 | 75 |
16* | 10,1 | 221 | 1,21 | 100 |
25* | 12,2 | 330 | 0,780 | 133 |
35* | 13,4 | 441 | 0,554 | 164 |
50 | 14,9 | 566 | 0,386 | 198 |
70 | 16,6 | 769 | 0,272 | 253 |
95 | 19,5 | 1028 | 0,206 | 306 |
120 | 20,6 | 1265 | 0,161 | 354 |
150 | 23,0 | 1558 | 0,129 | 393 |
185 | 26,2 | 1926 | 0,106 | 449 |
240 | 29,0 | 2471 | 0,0801 | 528 |
300 | 31,8 | 3068 | 0,0641 | 603 |
400 | 39,2 | 4149 | 0,0486 | 683 |
Installation in wall, on boards and in channels or embedded in plaster. Low level of smoke emission and corrosive gasses in case of fire.