Constructions

1-Conductor Fine-stranded copper (Class 5)
2-Insulation Cross linkable polyethylene (XLPE)
3-Outer sheath Low smoke zero halogen (LSZH)

Specifications

Min. bending radius 8 x D ≤ 25 mm²
Max. operating temperature 90°
Max. short circuit temperature 250°
Min. bending radius 12 x D > 25 mm²
Rated voltage Uo/U 450/750 V – 600/1000 V
AC test voltage 2,5 kV – 3,5 kV
Low smoke EN 61034
Halogen free EN 50525-1 – EN 50267
Flame propagation test on single cable EN 60332-1

Technical Data

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Conduit (A)
6381 B
 4* 6,9 81 4,95 42
6* 7,4 103 3,30 54
10* 8,9 157 1,91 75
16* 10,1 221 1,21 100
25* 12,2 330 0,780 133
35* 13,4 441 0,554 164
50 14,9 566 0,386 198
70 16,6 769 0,272 253
95 19,5 1028 0,206 306
120 20,6 1265 0,161  354
150 23,0 1558 0,129 393
185 26,2 1926 0,106 449
240 29,0 2471 0,0801 528
300 31,8 3068 0,0641 603
400 39,2 4149 0,0486 683

Applications

Installation in wall, on boards and in channels or embedded in plaster. Low level of smoke emission and corrosive gasses in case of fire.

Standards