Constructions
1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
2-Insulation | Polyvinyl chloride (PVC) |
3-Outer sheath | Polyvinyl chloride (PVC) |
1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
2-Insulation | Polyvinyl chloride (PVC) |
3-Outer sheath | Polyvinyl chloride (PVC) |
Min. bending radius | 10 x D |
Max. operating temperature | 70° |
Max. short circuit temperature | 160° |
AC test voltage | 2 kV |
Rated voltage Uo/U | 300/500 V |
Flame propagation test on single cable | EN 60332-1 |
Lead free | Pb |
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in | |
Lower Limit | Upper Limit | Air (A) | |||
BS 6004 FLAT TWIN (300/500 V) | |||||
2x1re | 3,9×6,1 | 4,8×7,4 | 60 | 18,1 | 13 |
2×1,5re | 4,4×7,0 | 5,3×8,5 | 75 | 12,1 | 16 |
2×1,5rm | 4,5×7,2 | 5,4×8,7 | 76 | 12,1 | 16 |
2×2,5re | 5,1×8,4 | 6,2×10,1 | 112 | 7,41 | 21 |
2×2,5rm | 5,2×8,5 | 6,3×10,3 | 113 | 7,41 | 21 |
2x4rm | 5,7×9,5 | 6,9×11,5 | 154 | 4,61 | 27 |
2x6rm | 6,4×10,8 | 7,8×13,0 | 203 | 3,08 | 34 |
2x10rm | 7,9×13,4 | 9,5×16,2 | 315 | 1,83 | 45 |
2x16rm | 8,9×15,4 | 10,8×18,6 | 448 | 1,15 | 57 |
3x1re | 3,9×8,4 | 4,8×10,1 | 85 | 18,1 | 13 |
3×1,5re | 4,4×9,6 | 5,3×11,7 | 106 | 12,1 | 16 |
3×2,5re | 5,1×11,6 | 6,2×14,0 | 159 | 7,41 | 21 |
3x4rm | 5,9×13,5 | 7,1×16,3 | 222 | 4,61 | 27 |
3x6rm | 6,4×15,1 | 7,8×18,2 | 293 | 3,08 | 34 |
3x10rm | 7,9×19,0 | 9,5×13,0 | 457 | 1,83 | 45 |
3x16rm | 8,9×21,8 | 10,8×26,3 | 654 | 1,15 | 57 |
Used as surface wiring where there is little mechanical damage risk, or in conduit.