H05V-K / H07V-K

Category:

Constructions

1-conductor Fine-stranded copper (Class 5)
2-insulation
Polyvinyl chloride (PVC)

Specifications

Min. bending radius D<8 ise 4xD   8<D<12 ise 5xD     D>12 ise 6xD
Max. operating temperature 70°
Max. short circuit temperature 160°
Rated voltage Uo/U 300/500 V – 450/750 V
AC test voltage 2 kV / 2,5 kV
Flame propagation test on single cable – EN 60332-1  EN 60332-1-2

Technical Data

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Conduit (A) Air (A)
H05V-K (300/500 V) / 2491X
0,5 2,0 9 39
0,75 2,2 12 26 16
1 2,4 13 19,5 11 20
H07V-K (450/750 V) / 6491X
1,5 2,8 19 13,3 14,5 24
2,5 3,4 30 7,98 19,5 32
4 3,9 44 4,95 26 42
6 4,4 63 3,30 34 54
10 6,1 112 1,91 46 73
16 7,4 169 1,21 61 98
25 9,0 251 0,780 80 129
35 10,9 369 0,554 99 158
50 12,7 528 0,386 119 198
70 14,7 730 0,272 151 245
95 16,9 969 0,206 182 292
120 18,8 1212 0,161 210 344
150 21 1521 0,129 240 391
185 23,3 1857 0,106 273 448
240 26,6 2443 0,0801 320 528
300 28,8 2818 0,0641 689
400 32,2 3635 0,0486 789

Applications

Used in closed and dry areas, switch and distribution boards, and also usen moving installations and equipments.

Standards