Constructions
| 1-conductor | Fine-stranded copper (Class 5) |
| 2-insulation | Cold resistant polyvinyl chloride (CR-PVC) |
| 1-conductor | Fine-stranded copper (Class 5) |
| 2-insulation | Cold resistant polyvinyl chloride (CR-PVC) |
| Min. bending radius | D<8 ise 4xD 8<D<12 ise 5xD D>12 ise 6xD |
| Max. operating temperature | 70° |
| Max. short circuit temperature | 160° |
| Rated voltage Uo/U | 300/500 V – 450/750 V |
| AC test voltage | 2 kV / 2,5 kV |
| Flame propagation test on single cable – EN 60332-1 | EN 60332-1-2 |
| Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in | |
| Conduit (A) | Air (A) | ||||
| H05V3-K (300/500 V) | |||||
| 0,50 | 2,1 | 9 | 39,0 | – | – |
| 0,75 | 2,3 | 12 | 26,0 | – | 16 |
| 1 | 2,5 | 14 | 19,5 | 12 | 20 |
| H07V3-K (450/750 V) | |||||
| 1,5 | 3,0 | 20 | 13,3 | 15 | 24 |
| 2,5 | 3,7 | 33 | 7,98 | 20 | 32 |
| 4 | 4,5 | 50 | 4,95 | 25 | 42 |
| 6 | 5,5 | 70 | 3,30 | 33 | 54 |
| 10 | 6,5 | 120 | 1,91 | 45 | 73 |
| 16 | 7,5 | 180 | 1,21 | 61 | 98 |
| 25 | 10,0 | 270 | 0,780 | 83 | 129 |
| 35 | 11,0 | 360 | 0,554 | 103 | 158 |
| 50 | 13,0 | 510 | 0,386 | 132 | 198 |
| 70 | 15,0 | 700 | 0,272 | 165 | 245 |
| 95 | 17,0 | 950 | 0,206 | 197 | 292 |
| 120 | 19,0 | 1150 | 0,161 | 235 | 344 |
| 150 | 21,0 | 1450 | 0,129 | – | 391 |
| 185 | 23,0 | 1750 | 0,106 | – | 448 |
| 240 | 27,0 | 2300 | 0,0801 | – | 528 |
Installation in surface mounted or embedded conduits or similar closed systems at low temperatures.