N2XFGbH

Constructions

1-Conductor Stranded copper (Class 2)
2-İnsulation Cross linkable polyethylene (XLPE)
3-Filler Halogen free flame retardant (HFFR)
4-Armour Galvanized flat steel wire (GSWA)
5-Bant Galvanized steel tape (GSTA)
6-Outer sheath Halogen free flame retardant (HFFR)

Specifications

Min. bending radius 12 x D
Max. operating temperature 90°
Max. short circuit temperature 250°
Rated voltage Uo/U 0.6/1 kV
AC test voltage 3,5 kV
Low smoke EN 61034
Halogen free EN 50525-1 – EN 50267
Flame propagation test on single cable EN 60332-3-24 Cat. C

Technical Data

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
N2XFGbH (0,6/1 kV)
 2×10 17,9 626 1,83 87 72
2×16 20,1 832 1,15 113 96
2×25 22,7 1129 0,727 146 130
2×35 24,9 1389 0,524 176 160
2×50 27,5 1741 0,387 208 195
2×70 31,5 2304 0,268 256 247
2×95 36,3 3097 0,193 307 305
2×120 38,9 3642 0,153 349 355
2×150 42,9 4488 0,124 391 407
2×185 48,5 5505 0,0991 442 469
2×240 54,3 6966 0,0754 509 551
2×300 59,1 8473 0,0601 581 643
 3×10 18,8 739 1,83 87 72
3×16 21,2 979 1,15 113 96
 3×25 24,0 1379 0,727 146 130
 3×35 26,4 1716 0,524 176 160
 3×50 29,4 2189 0,387 208 195
 3×70 33,7 2951 0,268 256 247
3×95 38,6 3936 0,193 307 305
3×120 41,6 4706  0,153 349 355
3×150 45,9 5804 0,124 391 407
3×185 52,1 7158 0,0991 442 469
3×240 58,1 9087  0,0754 509 551
3×300 63,3 11057 0,0601 581 643
3×16+10 22,1 1099  0,0470 667 737
3×25+16 25,1 1538 0,727/1,15 146 130
3×35+16 27,1 1886 0,524/1,15 176 160
3×50+25 30,4 2433 0,387/0,727 208 195
3×70+35 34,9 3287 0,268/0,524 256 247
3×95+50 39,9 4373 0,193/0,387 307 305
 3×120+70 43,4 5328 0,153/0,268 349 355
 3×150+70 47,0 6384 0,124/0,268 391 407
3×185+95 53,7 7976 0,0991/0,193 442 469
3×240+120 59,7 10084 0,0754/0,153 509 551
3×300+150 65,2 12339 0,0601/0,124 581 643
 4×10 20,1 872 1,83 87 72
4×16 22,8 1173 1,15 113 96
 4×25 25,9 1669 0,727 146 130
4×35 28,6 2095 0,524 176 160
 4×50 32,1 2706 0,387 208 195
 4×70 36,9 3693 0,268 256 247
 4×95 42,6 4986 0,193 307 305
 4×120 45,7 5921 0,153 349 355
4×150 50,6 7371 0,124 391 407
 4×185 57,3 9030 0,0991 442 469
 4×240 64,2 11525 0,0754 509 551
4×300 69,9 14161  0601 581  643
5×10 21,7 1020 1,83 87 72
5×16 24,6 1366 1,15 113 96
5×25 28,1 1958  0,727 146 130
5×35 31,3 2506 0,524 176 160
5×50 35,2 3257 0,387 208 195
5×70 40,5 4428 0,268 256 247
5×95 46,9 5983 0,193 307 305
5×120 50,5 7148 0,153 349 355
5×150 55,9 8894 0,124 391 407
5×185 63,4 10923 0,0991 442 469
5×240 71,1 14043 0,0754 509 551
5×300 77,6 17204 0,0601 581 643

Applications

Indoor installation, outdoor and underground installation in duct where better mechanical protection is required and places where the fire and toxic fumes can be a a threat. Suitable for underground and external installations.

Standards