Constructions
1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
2-Insulation | Polypropylene (PP) |
3-Filler | Halogen free flame retardant (HFFR) |
4-Outer sheath | Halogen free flame retardant (HFFR) |
1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
2-Insulation | Polypropylene (PP) |
3-Filler | Halogen free flame retardant (HFFR) |
4-Outer sheath | Halogen free flame retardant (HFFR) |
Min. bending radius | 12 x D |
Max. operating temperature | 70° |
Max. short circuit temperature | 160° |
Rated voltage Uo/U | 300/500 V |
AC test voltage | 2 kV |
Low smoke | EN 61034 |
Halogen free | EN 50525-1 – EN 50267 |
Flame propagation test on single cable | EN 60332-3-24 Cat. C |
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in |
Air (A) | ||||
NHMH (300/500 V) | ||||
2×1,5 | 7,9 | 96 | 12,1 | 22 |
2×2,5 | 8,7 | 126 | 7,41 | 30 |
2×4 | 10,0 | 178 | 4,61 | 40 |
2×6 | 11,0 | 231 | 3,08 | 51 |
2×10 | 13,8 | 376 | 1,83 | 70 |
2×16 | 16,4 | 545 | 1,15 | 98 |
3×1,5 | 8,3 | 115 | 12,1 | 22 |
3×2,5 | 9,2 | 154 | 7,41 | 30 |
3×4 | 10,6 | 222 | 4,61 | 40 |
3×6 | 12,0 | 302 | 3,08 | 51 |
3×10 | 14,6 | 477 | 1,83 | 70 |
3×16 | 17,6 | 709 | 1,15 | 98,5 |
4×1,5 | 8,9 | 138 | 12,1 | 18,5 |
4×2,5 | 9,9 | 187 | 7,41 | 25 |
4×4 | 11,9 | 286 | 4,61 | 34 |
4×6 | 13,5 | 390 | 3,08 | 43 |
4×10 | 15,8 | 594 | 1,83 | 60 |
4×16 | 19,4 | 897 | 1,15 | 80 |
5×1,5 | 9,6 | 164 | 12,1 | 18,5 |
5×2,5 | 10,7 | 224 | 7,41 | 25 |
5×4 | 13,2 | 355 | 4,61 | 34 |
5×6 | 14,6 | 470 | 3,08 | 43 |
5×10 | 17,2 | 723 | 1,83 | 60 |
5×16 | 21,5 | 1111 | 1,15 | 80 |
Refineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, populated business centers where there is a risk of fire.