VG-YMvKasmb

Constructions

1-Conductor Solid or stranded copper (Class 1 or Class 2)
2-Insulation Cross linkable polyethylene (XLPE)
3-Filler Polyvinyl chloride (PVC)
4-Inner sheath Polyvinyl chloride (PVC)
5-Armour Galvanized (flat) steel wire armour with copper aerth wires and a galvanized steel tape counter helix (GSWA)
6-Outer sheath Polyvinyl chloride (Flame retardant) (PVC-FR)

Specifications

Min. bending radius 12 x D
Max. operating temperature 90°
Max. short circuit temperature 250°
Rated voltage Uo/U 0.6/1 kV
AC test voltage 3,5 kV
Flame propagation test on single cable EN 60332-3-24 Cat. C
Lead free Pb

Technical Data

Cross Sectional Area mm² Class of Conductor Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Equivalent Copper Cross Section area of Armour/PE Conductor
VG-YMvKasmb (0,6/1 kV)
 2×1,5  1  14  350  12,1 1,5
 2×2,5 1 15 375  7,41 2,5
 2×4 1 16 445  4,61 4
 2×6 1 17 525  3,08 6
2×10 1 19 674  1,83 10
 2×10 2 20 812  1,83 10
 2×16 2 23 1049  1,15 16
 2×25 2 26 1419  0,727 16
 2×35 2 29 1800  0,524 16
 3×1,5 1 15 355  12,1 1,5
 3×2,5 1 15 415  7,41 2,5
3×4 1 16 490  4,61 4
 3×6 1 18 590  3,08 6
 3×10 1 20 895  1,83 10
 3×10 2 21 938  1,83 10
 3×16 2 24 1289  1,15 16
 3×25 2 27 1748  0,727 16
 3×35 2 31 2087  0,524 16
 4×1,5 1 15 390  12,1 1,5
 4×2,5 1 16 465  7,41 2,5
 4×4 1 17 650  4,61 4
 4×6 1 19 740  3,08 6
 4×10 1 21 1040  1,83 10
 4×10 2 22 1093  1,83 10
 4×16 2 25 1518  1,15 16
 4×25 2 30 2110  0,727 16
 4×35 2 33 2536  0,524 16
 5×1,5 1 16 420  12,1 1,5
 5×2,5 1 17 510  7,41 2,5
 5×4 1 19 670  4,61 4
 5×6 1 20 870  3,08 6
 5×10 1 22 1165  1,83 10
 5×10 2 24 1327  1,83 10
 5×16 2 27 1785  1,15 16
5×25 2 32 2470 0,727 16
5×35 2 37 3135 0,524 16

Applications

Power cable for industrial applications. Suitable for underground laying and where there is mechanical compulsion.

Standards