VO-YMvKasmb

Constructions

1-Conductor Solid or stranded copper (Class 1 or Class 2)
2-Insulation Cross linkable polyethylene (XLPE)
3-Filler Polyvinyl chloride (PVC)
4-Armour Galvanized round steel wire with an underlaying drain wire of tinned copper (GSWB)
5-Outer sheath Polyvinyl chloride (Flame retardant) (PVC-FR)

Specifications

Min. bending radius 10 x D
Max. operating temperature 90°
Max. short circuit temperature 250°
Rated voltage Uo/U 0.6/1 kV
AC test voltage 3,5 kV
Flame propagation test on single cable EN 60332-3-24 Cat. C
Lead free Pb

Technical Data

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Air (A)
 VO-YMvKasmb (0,6/1 kV)
 2×1,5+1,5 12,4 238 12,1 24
2×2,5+2,5 13,2 251 7,41 32
2×4+4 14,0 361 4,61 42
2×6+6 17,5 450 3,08 53
3×1,5+1,5 12,4 216 12,1 24
 3×2,5+2,5 13,2 293 7,41 32
3×4+4 15,5 425 4,61 42
3×6+6 19,2 535 3,08 53
4×1,5+1,5 13,5 321 12,1 24
4×2,5+2,5 14,4 334 7,41 32
4×4+4 15,5 444 4,61 42
4×6+6 19,2 574 3,08 53

Applications

Power cable for use in industrial applications. Suitable for underground laying.

Standards