YVOV (NYRY) / YVZ2V

Constructions

1-Conductor Solid or stranded copper (Class 1 or Class 2)
2-Insulation Polyvinyl chloride (PVC)
3-Filler Polyvinyl chloride (PVC)
4-Armour Galvanized round steel wire (GSWA)
5-Outer sheath Polyvinyl chloride (PVC)

Specifications

Min. bending radius 12 x D
Max. operating temperature 70°
Max. short circuit temperature 160°
Rated voltage Uo/U 0.6/1 kV
AC test voltage 3,5 kV
Flame propagation test on single cable EN 60332-1

Technical Data

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YVOV (NYRY) (0,6/1 kV)
2×1,5 13,5 331 12,1  32 20
2×2,5 14,5 380 7,41 42 27
2×4 16,0 500 4,61 52 37
2×6 18,0 700 3,08 68 48
 2×10 20,5 900 1,83 90 66
2×16 22,5 1100 15 116 89
2×25 26,0 1650 0,727 150 118
2×35 28,0 1950 0,524 181 145
2×50 31,5 2500 0,387 215 176
2×70 35,5 3400 0,268 264 224
2×95 40,5 4360 0,193 317 271
3×1,5 14,0 350 12,1 26 18,5
3×2,5 15,0 420 7,41 34 25
 3×4 17,5 670 4,61 44 34
3×6 18,5 780 3,08 56 43
 3×10 21,5 1050 1,83 75 60
3×16 23,5 1300 1,15 98 80
 3×25 27,5 1950 0,727 128 106
 3×35 29,5 2350 0,524 157 131
 3×50 33,5 3050 0,387 185 159
 3×70 38,0 4200 0,268 228 202
3×95 43,0 5350 0,193 275 244
3×120 46,5 6400 0,153 313 282
 3×150 52,0 8150 0,124 353 324
3×185 57,0 9750 0,0991 399 371
 3×240 67,0 12250  0,0754 464 436
 3×10/6 23,0  1280 1,83/3,08  75 60
3×16/10 25,5 1600 1,15/1,83 98 80
3×25/16 28,5 2150 0,727/1,15 128 106
3×35/16 30,5 2550 0,524/1,15 157 131
3×50/25 35,5 3600 0,387/0,727 185 159
3×70/35 39,5 4650  0,268/0,524 228 202
3×95/50 44,5 5950 0,193/0,387 275 244
 3×120/70 50,5 7700 0,153/0,268 313 282
 3×150/70 53,5 8900  0,124/0,268 353 324
3×185/95 59,0 10800 0,0991/0,193 399 371
3×240/120 66,5 13500 0,0754/0,153 464 436
4×1,5 15,0 400 12,2 26 1,5
 4×2,5 15,5 480 7,41 34 25
 4×4 18,5 770 4,61 44 34
 4×6 20,0 900 3,08 56 43
 4×10 23,0 1200 1,83 75 60
4×16 26,0 1700 1,15 98 80
 4×25 29,5 2300 0,727 128 106
4×35 32,5 2870 0,524 157 131
 4×50 37,5 4000 0,387 185 159
 4×70 41,5 5150 0,268 228 202
 4×95 48,0 7050 0,193 275 244
 4×120 52,5 8450 0,153 313 282
4×150 57,0 10050 0,124 353 324
 4×185 63,0 12150 0,0991 399 371
 4×240 70,5 15300 0,0754 464 436
5×1,5 15,2 473 12,1 27 19,5
 5×2,5 17,0 647 7,41 36 25
5×4 18,1 794 4,61 47 34
5×6 20,8 1030 3,08 59 43
 5×10 24,8 1551 1,83 79 59
 5×16 27,4 1992 1,15 102 79
 5×25 31,7 2743 0,727 133 106
 5×32 35,7 3660 0,524 159 129
5×50 40,9 4755 0,387 188 157
5×70 45,2 6131 0,268 232 199
5×95 52,8 8490 0,193 280 246
5×120 57,7 10250 0,153 318 285
 6×1,5 17,0  625 12,1 16,9  13
 7×1,5 17,7 673 12,1 15,6 12
 7×2,5 18,9 797 7,41 20,4 16,3
 7×4 21,8 1095 4,61 26,4 22,1
7×6 24,1 1346 3,08 38 45
 8×1,5  18,5  740 12,10 14,3 11,1
 8×2,5 20,4 920 7,41 18,7 15,0
 10×1,5 18,7 811 12,10 13 10,2
 10×2,5 23,80 1286 7,41 17,0 13,8
12×1,5 22,30 1109  12,10 12,3 9,7
 12×2,5 24,00 1329  7,41 16,2 13,1
 19×1,5 25,20 1421  12,10 10,4 8,3
 19×2,5 27,30 1736  7,41 13,6 11,3
24×1,5 27,0 1600  12,10 9,1 7,4
24×2,5 31,50 2238  7,41 11,9 10,0
27×1,5 27,5 1700  12,10 8,8 7,2
 27×2,5 34,70 2753  7,41 11,6 9,7
30×1,5 33,00 2349  12,10 8,6 7,0
30×2,5 31,0 2250  7,41 11,2 9,4
40×1,5 35,40 2712  12,10 7,8 6,5
40×2,5 35,0 3000  7,41 10,2 8,8
48×1,5 34,5 2750  12,10 7,3 6,1
48×2,5 42,84 4220,0  7,41 9,5 8,3

Applications

Can be used in underground installations since the cable is very suitable for mechanical compulsion and harsh operating conditions .

Standards