Constructions
1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
2-Insulation | Cross linkable polyethylene (XLPE) |
3-Outer sheath | Polyvinyl chloride (PVC) |
1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
2-Insulation | Cross linkable polyethylene (XLPE) |
3-Outer sheath | Polyvinyl chloride (PVC) |
Min. bending radius | 4 x D ≤ 25 mm² |
Max. operating temperature | 90° |
Max. short circuit temperature | 250° |
Min. bending radius | 6 x D > 25 mm² |
Rated voltage Uo/U | 600/1000 V |
AC test voltage | 2,5 kV – 3,5 kV |
Flame propagation test on single cable | EN 60332-1 |
Lead free | Pb |
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in |
Conduit (A) | ||||
6181 XY | ||||
1,5 * | 4,4 | 31 | 12,2 | 23 |
2,5 * | 4,8 | 42 | 7,41 | 31 |
4 * | 5,7 | 63 | 4,61 | 42 |
6* | 6,2 | 83 | 3,08 | 54 |
10* | 7,1 | 124 | 1,83 | 75 |
16* | 8,4 | 188 | 1,15 | 100 |
25* | 9,9 | 281 | 0,727 | 133 |
35* | 10,9 | 374 | 0,524 | 164 |
50* | 13,0 | 518 | 0,387 | 198 |
70* | 14,7 | 723 | 0,268 | 253 |
95* | 16,6 | 973 | 0,193 | 306 |
120* | 18,5 | 1217 | 0,153 | 354 |
150* | 20,4 | 1495 | 0,124 | 393 |
185* | 22,2 | 1848 | 0,0991 | 449 |
240* | 25,4 | 2404 | 0,0754 | 528 |
300* | 28,9 | 3125 | 0,0601 | 603 |
Installation in walls, on boards and in channels or embedded in plaster.