Constructions
| 1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
| 2-Insulation | Polyvinyl chloride (PVC) |
| 3-Outer sheath | Polyvinyl chloride (PVC) |
| 1-Conductor | Solid or stranded copper (Class 1 or Class 2) |
| 2-Insulation | Polyvinyl chloride (PVC) |
| 3-Outer sheath | Polyvinyl chloride (PVC) |
| Min. bending radius | 8 x D ≤ 25 mm² |
| Max. operating temperature | 70° |
| Max. short circuit temperature | 160° |
| Min. bending radius | 12 x D > 25 mm² |
| Rated voltage Uo/U | 300/300 V |
| AC test voltage | 2 kV |
| Flame propagation test on single cable | EN 60332-1 |
| Lead free | Pb |
| Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in |
| Conduit (A) | ||||
| 6181 Y | ||||
| 1* re | 3,9 | 26 | 18,1 | 13,5 |
| 1,5* re | 4,4 | 33 | 12,1 | 19,5 |
| 2,5* re | 5,0 | 46 | 7,41 | 24 |
| 4* rm | 6 | 69 | 4,61 | 32 |
| 6* rm | 6,5 | 89 | 3,08 | 41 |
| 10* rm | 7,8 | 139 | 1,83 | 57 |
| 16* | 9,1 | 207 | 1,15 | 76 |
| 25* | 11 | 312 | 0,727 | 101 |
| 35* | 12,1 | 410 | 0,524 | 125 |
| 50 | 13,8 | 557 | 0,387 | 151 |
| 70 | 15,6 | 761 | 0,268 | 192 |
| 95 | 18,2 | 1060 | 0,193 | 232 |
| 120 | 19,9 | 1307 | 0,153 | 269 |
| 150 | 21,8 | 1599 | 0,124 | 300 |
| 185 | 23,8 | 1977 | 0,0991 | 341 |
| 240 | 27,8 | 2608 | 0,0754 | 400 |
| 300 | 32,5 | 3355 | 0,0601 | 458 |
Installation in walls, on boards and in channels or embedded in plaster.