Constructions
1-Conductor | Fine-stranded copper (Class 5) |
2-Insulation |
Polyvinyl chloride (PVC)
|
3-Outer sheath | Polyvinyl chloride (PVC) |
1-Conductor | Fine-stranded copper (Class 5) |
2-Insulation |
Polyvinyl chloride (PVC)
|
3-Outer sheath | Polyvinyl chloride (PVC) |
Min. bending radius | 8 x D |
Max. operating temperature | 70° |
Max. short circuit temperature | 160° |
Rated voltage | 300/500 V |
AC test voltage | 2 kV |
Rated voltage | 300/500 V |
Flame propagation test on single cable | EN 60332-1 |
Lead free | Pb |
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in |
Air (A) | ||||
NYIFY-F (300/500 V) | ||||
2×1 | 4,0 x 9,3 | 56 | 19,5 | 13 |
2×1,5 | 4,4 x 10,6 | 77 | 13,3 | 16 |
12×2,5 | 5,0 x 12,0 | 106 | 7,98 | 21 |
2×4 | 5,6 x 14,1 | 142 | 4,95 | 27 |
3×1 | 4,0 x 14,9 | 84 | 19,5 | 13 |
3×1,5 | 4,9 x 17,6 | 108 | 13,3 | 16 |
3×2,5 | 5,0 x 19,6 | 148 | 7,98 | 21 |
3×4 | 5,6 x 23,1 | 199 | 4,95 | 27 |
Suitable for dry and humid areas. All type of factory, warehouse and depots where is fire and explosion threat. Not suitable for underground. Used in fixed installations laying in conduit on and under plaster.