624-Y

Constructions

1-Conductor Solid or stranded copper (Class 1 or Class 2)
2-Insulation
Polyvinyl chloride (PVC)
3-Outer sheath Polyvinyl chloride (PVC)

Specifications

Min. bending radius 8 x D
Max. operating temperature 70°
Max. short circuit temperature 160°
Rated voltage Uo/U 450/750 V – 600/1000 V
AC test voltage 2 kV
Rated voltage Uo/U 300/500 V
Flame propagation test on single cable EN 60332-1
Lead free Pb

Technical Data

Cross Sectional Area mm² Mean Overall Dimension mm Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Lower Limit Upper Limit Air (A)
624-Y (300/500 V)
1x1re 3,9×5,0 4,8×6 41 18,1/18,1 13
1×1,5+1re 4,4×5,4 5,3×6,6 48 12,1/18,1 16
1×1,5+1rm 4,5×5,5 5,4×6,7 49 12,1/18,1 16
2×1+1re 3,9×7,2 4,8×8,7 67 18,1/18,1 13
2×1,5+1re 4,4×8,1 5,3×9,7 83 12,1/18,1 16
2×1,5+1rm 4,5×8,3 5,4×10,0 84 12,1/18,1 16
2×2,5+1,5re 5,1×9,6 6,2×11,7 120 7,41/12,1 21
2×2,5+1,5rm 5,2×9,8 6,3×11,9 121 7,41/12,1 21
2×4+1,5rm 5,7×10,8 6,9×13,1 172 4,61/12,1 27
2×6+2,5rm 6,4×12,4 7,8×15,0 235 3,08/7,41 34
2×10+4rm 7,9×15,6 9,5×18,9 373 1,83/4,61 45
2×16+6rm 8,9×18,1 10,8×21,9 529 1,15/3,08 57
3×1+1re 3,9×9,4 4,8×11,4 91 18,1/18,1 13
3×1,5+1re 4,4×10,7 5,3×12,9 117 12,1/18,1 16
3×2,5+1,5re 5,1×12,6 6,2×15,3 172 7,41/12,1 21
3×4+1,5rm 5,9×14,8 7,1×17,9 243 4,61/12,1 27
3×6+2,5rm 6,4×16,8 7,8×20,2 315 3,08/7,41 34
3×10+4rm 7,9×21,3 9,5×25,7 516 1,83/4,61 45
3×16+6rm 8,9×24,6 10,8×29,7 735 1,15/3,08 57

Applications

Used as surface wiring where there is little mechanical damage risk, or in conduit.

Standards